LOW VOLTAGE INSTALLATION CABLES 450/750 V |
| CABLE DESCRIPTION |
Application: These cables are suitable for installation underground, in buildings, in cable trays and in the open air where better mechanical protection is required. |
Characteristics:
- Solid conductors
- PVC insulation
- PVC filling
- Steel tape armour
- PVC outer sheath |
| CONSTRUCTION |
| Conductor: |
Solid circular annealed copper conductor |
| |
|
| Insulation: |
Lead-free PVC insulation |
| |
|
| Colouring: |
3-cores: Green/yellow, Blue, Brown
4-cores: Green/yellow, Blue, Brown, Black
* 4-cores: Green/yellow, Brown, Black, Grey
5-cores: Green/yellow, Blue, Brown, Black, Grey
>5-cores: Green/yellow, Black with consecutive numbers
* optional |
| |
|
| Filling: |
Lead-free PVC filling compound |
| |
|
| Armour: |
2 Layers of galvanised steel tape |
| |
|
| Outer sheath: |
Lead-free PVC compound |
| |
|
| Colour: |
Grey |
| |
|
| DIMENSIONS |
| Construction |
|
Nominal Insulation thickness |
Thickness of armour tape |
Nominal thickness of sheath |
Nominal outer diameter |
Approx. Weight |
Approx. amount of PVC and ftalates |
| Conductor diameter |
mm |
mm |
mm |
mm |
kg/km |
kg/km |
| 3 x 1.5 mm² |
(1 / 1.38 mm) |
0.8 |
0.2 |
1.0 |
10.4 |
234 |
130.8 |
| 4 x 1.5 mm² |
(1 / 1.38 mm) |
0.8 |
0.2 |
1.0 |
11.2 |
243 |
149.4 |
| 5 x 1.5 mm² |
(1 / 1.38 mm) |
0.8 |
0.2 |
1.0 |
12.0 |
270 |
144.8 |
| 7 x 1.5 mm² |
(1 / 1.38 mm) |
0.8 |
0.2 |
1.0 |
12.9 |
326 |
128.8 |
| 5 x 2.5 mm² |
(1 / 1.75 mm) |
0.8 |
0.2 |
1.0 |
13.0 |
340 |
165.6 |
| 3 x 4 mm² |
(1 / 2.26 mm) |
0.9 |
0.2 |
1.0 |
14.5 |
336 |
174.0 |
| 4 x 4 mm² |
(1 / 2.26 mm) |
0.9 |
0.2 |
1.1 |
16.0 |
417 |
195.2 |
| 3 x 6 mm² |
(7 / 1.04 mm) |
0.9 |
0.2 |
1.1 |
17.0 |
469 |
234.1 |
| 4 x 6 mm² |
(7 / 1.04 mm) |
0.9 |
0.2 |
1.1 |
18.0 |
562 |
262.5 |
| 3 x 10 mm² |
(7 / 1.35 mm) |
1.1 |
0.2 |
1.2 |
20.0 |
696 |
336.4 |
| 4 x 10 mm² |
(7 / 1.35 mm) |
1.1 |
0.2 |
1.2 |
22.0 |
861 |
393.1 |
| 3 x 16 mm² |
(7 / 1.70 mm) |
1.1 |
0.2 |
1.2 |
22.5 |
965 |
428.5 |
| 4 x 16 mm² |
(7 / 1.70 mm) |
1.1 |
0.2 |
1.3 |
24.5 |
1186 |
487.2 |
| 3 x 25 mm² |
(7 / 2.13 mm) |
1.3 |
0.2 |
1.4 |
27.0 |
1353 |
579.3 |
| 4 x 25 mm² |
(7 / 2.13 mm) |
1.3 |
0.2 |
1.4 |
29.5 |
1667 |
645.0 |
| 3 x 35 mm² |
(19 / 1.53 mm) |
1.3 |
0.2 |
1.5 |
30.0 |
1836 |
747.9 |
| 4 x 35 mm² |
(7 / 1.53 mm) |
1.3 |
0.2 |
1.5 |
33.0 |
2347 |
930.8 |
|
| |
|
| TECHNICAL DATA |
| ELECTRICAL CHARACTERISTICS (at 20°C) |
| Conductor resistance: |
IEC 60228 Class 1 |
|
| |
|
|
| Rated voltage: |
450/750 |
Volt |
| |
|
|
| Test voltage: |
2500 |
Volt a.c. |
| |
|
|
|
| GENERAL TECHNICAL INFORMATION |
| Max. conductor temperature: |
70 °C |
| |
|
| Max. short circuit temperature: |
150 °C |
| |
|
| Fire performance: |
IEC 60332-1 |
| |
|
Bending radius (in mm):
D = The outer diameter (in mm) |
During repositioning: 7 x D
During installation (once-only): 4 x D |
| |
|
| Maximum pulling force (in N): |
Using a pulling head: 50 x S¹)
Using a cable stocking: 3 x D² (max. 10 kN) |
| |
|
Temperature range:
Storage and service temperature:
Minimal cable temperature during installation: |
-25 °C to 55 °C
-5 °C |
| |
|
|
| ADDITIONAL INFORMATION |
| The cables have been constructed and tested in accordance with the following: |
| - Conductors |
IEC 60228 Class 1 |
Approximate colours: |
| |
HD 383 Class 1 |
- Cores |
Blue: |
RAL 5012 |
| - Construction |
DS 2393-3 |
|
Brown: |
RAL 8003 |
| - Testing |
DS 2393-2 |
|
Black: |
RAL 9004 |
| |
IEC 60811 |
|
Grey: |
RAL 7035 |
| - Fire characteristics |
EN 50265-1 |
|
Green/Yellow: |
RAL 6018/1021 |
| |
HD 405.1 |
|
|
|
| |
IEC 60332-1 |
- Sheath |
Light Grey: |
RAL 7047 |
| - Marking |
DS 2393-1 |
|
| 1) Total cross section of conductors (in mm²), for example 3 x 2.5=7.5 mm² |